CU/PVC /PVC (TWIN & 3 CORE FLAT CABLES)
S. No
Number of cores
No.
Nominal cross-sectional Area
mm2
Maximum DC Conductor Resistance at 20°C
Ω/km
Nominal Insulation Thickness
mm
Nominal sheath Thickness
mm
Approx. Overall Diameter
mm
Approx. Net Weight
Kg/km
Bar Code
1
2
1.5
12.1
0.7
0.9
4.6 X 7.5
71
2
2
2.5
7.41
0.8
1
5.6 X 9.3
110
3
2
4
4.61
0.8
1
6.3 X 10.5
150
4
2
6
3.08
0.8
1.1
7.0 X 11.8
220
5
2
10
1.83
1
1.2
8.5 X 14.5
350
6
2
16
1.15
1
1.3
9.6 X 17
510
11
3
1.5
12.1
0.7
0.9
4.6 X 10.5
110
12
3
2.5
7.41
0.8
1
5.6 X 12.8
170
13
3
4
4.61
0.8
1.1
6.3 X 14.5
220
14
3
6
3.08
0.8
1.1
7.0 X 16.7
310
15
3
10
1.83
1
1.2
8.5 X 20.5
505
16
3
16
1.15
1
1.3
9.7 X 24
750